The Google Cloud outage in London on 20 October 2026 was caused by an external underground cable fault that cut utility power to a site in zone europe-west2-b. A second feed was offline for repairs and generators failed to start because of controller wiring, so the zone lost power for about six hours.
Table of contents 5 sections
- Google Cloud's europe-west2 London region suffered a 6 hour 8 minute incident starting late on 19 October 2026, Pacific time.
- An underground cable fault cut utility power while the backup feed was offline for repairs and generators failed to start.
- Revolut, Lloyds, HSBC and Halifax customers and HM Courts and Tribunals Service video links were affected.
- Google reported more than 99 percent of Compute Engine VMs healthy by the end of the incident.
- Google plans to check controller configurations at similar sites worldwide by 15 November.
The Google Cloud outage in London that disrupted Revolut, several UK banks and court video hearings on 20 October 2026 started with a damaged underground cable outside a data centre, according to Google's final incident report. Backup generators should have taken over within seconds. They never started, and one of the three zones in the europe-west2 region went dark for hours.
Google lists the incident as running for 6 hours and 8 minutes, from 23:00 on 19 October to 05:08 the next morning, Pacific time. In UK terms, that is roughly from just after 7am to early afternoon on a Tuesday working day.
What caused the Google Cloud outage in London
The incident report on Google's status dashboard describes a chain of failures rather than a single fault:
- At 22:53 Pacific time, an external underground cable fault on utility feed A cut primary power to the site.
- The second utility feed, B, was not available. Its breaker had been opened and locked out for repairs after a generator load test on 14 October, so the site was running on one feed.
- The generators did not start. The controllers that sense undervoltage were wired upstream of the isolated feed B breaker, so they still saw live voltage and never issued a start command.
- Uninterruptible power supply batteries, with about five minutes of runtime, ran down, and at 23:00 the hosts in zone europe-west2-b lost power.
That last detail is the uncomfortable one. Redundancy existed on paper: two utility feeds, generators and batteries. A maintenance state and a wiring choice in the control logic meant none of it worked when it was needed. Google's preliminary report on 22 October first blamed a startup fault in the controllers; the final version pinned it on that configuration.
Who the Google Cloud outage hit, and why it spread
Zonal resources in europe-west2-b were simply unavailable: Compute Engine virtual machines, zonal Kubernetes clusters, non-high-availability Cloud SQL databases and zonal persistent disks among them. Google says some customers' automatic failovers also failed because of capacity limits and the difficulty of replicating storage.
The other two London zones did not lose power, but they did not escape. Google describes demand surges, dependencies between zones and HTTP 500 and 503 errors as workloads tried to move. Monitoring firm StatusGator counted 171 services showing signs of impact, 50 of which cited Google Cloud directly in their own status updates.
The public saw it through apps. The Irish News reported that Revolut customers had problems with card payments, transfers, cash withdrawals and signing in, with more than 1,500 people reporting Revolut problems to Downdetector. Lloyds, HSBC and Halifax customers also reported issues, as did users of Royal Mail, DPD and Rightmove. HM Courts and Tribunals Service's cloud video platform, used for remote links into hearings in England and Wales, went down. Google said: "We apologise to all who are affected by the disruption." Revolut told Euronews that "all our customers' money and data are safe."
How long recovery took
Restoring power was the quick part of ending the Google Cloud outage. A standby utility source was back at 23:54 Pacific time and power to the data hall at 00:20, after a controller reset. Bringing machines back cleanly took far longer, because storage systems had shut down uncleanly. Controlled traffic returned to the zone from 03:45, new virtual machines could be created again at 04:46, and by 05:08 Google reported more than 99 percent of Compute Engine VMs healthy.
Google says it saw no impact outside europe-west2. A small number of customers were still dealing with problems later on 20 October and were told to open support cases.
What Google says it is changing
The report lists completed and pending fixes. The damaged cable was located on 26 October, the controllers were reconfigured and tested, and on-site emergency procedures were rewritten and practised. Pending items include repairing the cable by 30 October, returning the site to its normal dual-feed setup by 31 October, a maintenance freeze at similar sites and, by 15 November, a check of controller configurations at comparable sites around the world. Google also promises faster automated customer notices for location-wide incidents.
That global check is the item worth watching. If the same wiring pattern exists elsewhere, the London failure was a warning shot for other regions.
What this means for anyone running on one cloud region
Dr Amro Al-Said Ahmad, a computer science lecturer at Keele University, told The Register that resilience requires multi-region deployments, workload portability and disaster recovery that has actually been tested. The incident backs him up. A single zone failing is exactly what cloud architecture is supposed to absorb, yet failovers stumbled on capacity and cross-zone dependencies.
For teams on IaaS or PaaS platforms, the practical checks are concrete: confirm which services you run are zonal rather than regional, test what happens when a zone vanishes, and make sure a second region has enough reserved capacity to take the load. Cloud is now a central business for Google's parent, as our look at Alphabet's third quarter explains, and customers paying for it are entitled to ask harder questions about the physical plant underneath.
Next, watch for Google's confirmation that the London site is back on two feeds by 31 October and for the results of its worldwide controller review in mid-November. Banks and payment apps that leaned on a single London zone will face questions from their own customers about why one power failure could stop card payments.
Frequently asked
- Multiple services were experiencing issues in the europe-west2 region — Google Cloud Service Health
- Banks and courts affected by disruption as Google apologises for cloud outage — The Irish News
- Google Cloud London zone outage — The Register
- Google Cloud outage on October 20, 2026: a europe-west2 power event and 171 possibly affected services — StatusGator